https://repositorio.ufjf.br/jspui/handle/ufjf/6510
Fichero | Descripción | Tamaño | Formato | |
---|---|---|---|---|
ramonreissiqueiradeoliveira.pdf | 4.63 MB | Adobe PDF | Visualizar/Abrir |
Clase: | Dissertação |
Título : | Detecção de ilhamento em redes com geração distribuída por injeção de pequenos sinais na rede elétrica |
Autor(es): | Oliveira, Ramon Reis Siqueira de |
Orientador: | Duque, Carlos Augusto |
Co-orientador: | Ribeiro, Paulo Fernando |
Miembros Examinadores: | Silva, Leandro Rodrigues Manso |
Miembros Examinadores: | Barbosa, Pedro Gomes |
Miembros Examinadores: | Lima, Antonio Carlos Siqueira de |
Resumo: | Uma rede com vários geradores distribuídos conectados pode melhorar a eficiência energética e reduzir o impacto negativo na rede elétrica. Um problema que surge é quando o fornecimento de energia principal é desconectado do sistema, diz-se então que ocorreu um ilhamento. Essa situação é indesejada, pois pode provocar problemas em termos de qualidade de energia, segurança, tensão e estabilidade de frequência. Esse trabalho tem por finalidade identificar o ilhamento pela variação da impedância do sistema, utilizando um método proposto que utiliza uma técnica de estimação de impedância através da injeção de um pequeno sinal na tensão de saída do gerador distribuído. Os testes realizados mostraram que quanto maior for a contribuição do inversor na potência fornecida para a carga, melhores são os valores estimados de impedância e na presença de dois inversores, os sinais injetados por cada um deles devem estar em frequências harmônicas o mais distante possível, para melhores resultados na estimação da impedância. Além disso, quando o fluxo de potência da rede para a carga é próximo de zero, o método foi capaz de identificar o ilhamento mesmo cosem atuação dos relés de tensão e frequência. O ilhamento é possível de ser identificado em aproximadamente 0,5 s em todos os casos testados, estando dessa forma dentro do tempo máximo estabelecido nas normas. |
Resumen : | A grid with multiple distributed generators can improve energy efficiency and reduce the negative impact on itself. One problem that occurs is when the main power supply is disconnected from the system, this is called islanding. This is undesirable because it can cause problems in terms of power quality, safety, voltage and frequency stability. This work aims to identify the islanding by the system impedance variation, using a proposed method that uses an impedance estimation technique, injecting a small signal into the output voltage of the distributed generator. The tests performed showed as higher the contribution of the inverter to the power supplied to the load as better the estimated impedance values. In the presence of two inverters, the signals injected by each of them must be in harmonic frequencies, for better impedance estimation results. In addition, when the utility energy flow to the load is close to zero, the method was able to identify the same island as the voltage and frequency relays. The island can be identified in approximately 0.5 s in all cases tested, thus being within the maximum time limit set in the standards. |
Palabras clave : | Geração distribuída Inversor Máquina síncrona Ilhamento Injeção de sinais Transformada de fourier Estimação de impedância Distributed generation Inverter Synchronous machine Islanding Signal injection Fourier transform Impedance estimation |
CNPq: | CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA |
Idioma: | por |
País: | Brasil |
Editorial : | Universidade Federal de Juiz de Fora (UFJF) |
Sigla de la Instituición: | UFJF |
Departamento: | Faculdade de Engenharia |
Programa: | Programa de Pós-graduação em Engenharia Elétrica |
Clase de Acesso: | Acesso Aberto |
URI : | https://repositorio.ufjf.br/jspui/handle/ufjf/6510 |
Fecha de publicación : | 18-dic-2017 |
Aparece en las colecciones: | Mestrado em Engenharia Elétrica (Dissertações) |
Los ítems de DSpace están protegidos por licencias Creative Commons, con todos los derechos reservados, a menos que se indique lo contrario.