Please use this identifier to cite or link to this item: https://repositorio.ufjf.br/jspui/handle/ufjf/1786
Files in This Item:
File Description SizeFormat 
brunomontesanoschettino.pdf5.22 MBAdobe PDFThumbnail
View/Open
Type: Dissertação
Title: Uma proposta para detecção e compensação dos efeitos causados pela saturação dos núcleos dos transformadores de corrente utilizados em circuitos de proteção
Author: Schettino, Bruno Montesano
First Advisor: Duque, Carlos Augusto
Co-Advisor: Silveira, Paulo Márcio da
Referee Member: Barbosa, Pedro Gomes
Referee Member: Bretas, Arturo Suman
Resumo: Este trabalho apresenta uma proposta para efetuar a compensação dos efeitos causados pela saturação dos núcleos dos Transformadores de Corrente (TC) utilizados em circuitos de proteção, através da correção do valor eficaz da componente alternada da corrente distorcida do secundário. O problema foi dividido em duas etapas: a detecção e a compensação da saturação. Para a etapa de detecção foi desenvolvido um método novo, denominado método da função primeira diferença do filtro de Lanczos, que mostrou-se mais imune a ruídos que os métodos tradicionais existentes na literatura. Na etapa de compensação da saturação, foi utilizado o método de estimação para modelos lineares. Os métodos foram implementados em MATLAB e testados em correntes distorcidas geradas de duas formas distintas: através de um simulador de TC operando na região de saturação desenvolvido em MATLAB e através de simulações realizadas em um simulador digital em tempo real (RTDS). Os resultados preliminares apontam para um algoritmo robusto, independente das características dinâmicas do TC, da corrente de falta e de outros fatores externos. Além disso, o tempo de resposta mostrou-se compatível com a possibilidade de implementação em tempo real, atendendo às necessidades da área de proteção dos Sistemas Elétricos de Potência.
Abstract: This work presents a proposal to perform a compensation of the effects due to saturation of Current Transformers (CT) cores used in circuit protection, by correcting the root mean square (RMS) value of the alternate component (AC) of the secondary distorted current. The problem was divided into two phases: detection and compensation of saturation. For the step of detection, a new method was developed, called first difference function of Lanczos filter method, which has proved more immune to noise than traditional methods in the literature. In the step of compensation of saturation, was used a estimation method for linear models. The methods were implemented in MATLAB and tested on distorted currents generated in two ways: through a CT simulator operating in the saturation region developed in MATLAB and through simulations in a real time digital simulator (RTDS). Preliminary results indicate a robust algorithm, independent of the dynamic characteristics of TC, fault current and other external factors. Furthermore, the response time was showed compatible with the possibility of real time implementation, attending to the needs of the protection area of Electric Power Systems.
Keywords: Transformador de Corrente
Saturação
Detecção
Compensação
Proteção de Sobrecorrente
Current Transformer
Saturation
Detection
Compensation
Overcurrent Protection
CNPq: CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA
Language: por
Country: Brasil
Publisher: Universidade Federal de Juiz de Fora
Institution Initials: UFJF
Department: Faculdade de Engenharia
Program: Programa de Pós-graduação em Engenharia Elétrica
Access Type: Acesso Aberto
URI: https://repositorio.ufjf.br/jspui/handle/ufjf/1786
Issue Date: 3-Dec-2012
Appears in Collections:Mestrado em Engenharia Elétrica (Dissertações)



Items in DSpace are protected by Creative Commons licenses, with all rights reserved, unless otherwise indicated.