Detecção, identificação e correção de erros grosseiros de medição em redes de distribuição desequilibradas utilizando multiplicadores de Lagrange
Loading...
Date
Journal Title
Journal ISSN
Volume Title
Publisher
Universidade Federal de Juiz de Fora (UFJF)
DOI
Abstract
This work addresses detecting, identifying, and correcting gross errors (EG) in unbalanced
three-phase electrical systems. Unbalanced three-phase electrical systems are standard in
power distribution networks, where unbalanced loads, connection issues, and component
failures can lead to imbalances in electrical quantities such as voltages and currents.
A method is proposed that applies state estimation (E-OPFT) to detect, identify, and
correct these gross errors in unbalanced electrical systems. The method utilizes Lagrange multipliers (ML) related to the lower and upper bounds of the measured variables,
thereby calculating error indices related to these bounds. Initially, the developed method
implements gross error detection algorithms that identify inconsistent patterns in the
measurements. Subsequently, identification algorithms are applied to determine the buses
that have gross errors. This step is performed through Modified E-OPFT (E-OPFT-m).
At the end of E-OPFT-m, the ML values corresponding to the lower and upper margins
are found, and with them, the respective error indices (IND) of the measurements are
calculated, and when non-zero values are encountered, it indicates that the measurement contains an error. The correction step uses the mean error, which depends on the
identified error and the meter uncertainty, to determine pseudo-measurements, which
are considered as the new measurements for estimation, and finally applies it to Final
E-OPFT (E-OPFT-f). This technique allows correcting the incorrect measurements and
re-estimating the system states, aiming to provide more accurate and reliable estimates
of the electrical quantities. The dissertation also presents case studies and simulations
in modified 4-bus and 33-bus systems to validate the effectiveness and robustness of the
proposed method. The results show that the method is capable of accurately detecting
and correcting gross errors in unbalanced three-phase electrical systems, contributing to
the performance and safety of these systems. In summary, this work contributes to the
advancement of the detection, identification, and correction of gross errors in unbalanced
three-phase electrical systems, offering a new method based on state estimation and
Lagrange multipliers. The obtained results demonstrate the feasibility and efficiency of
the proposed method, providing significant benefits to the electrical sector in terms of
safety and operational efficiency.