In the most used transmission configurations for offshore wind farms, the generating
units are connected in parallel, transmitting the energy to an offshore substation, where
the voltage is increased and then transmitted to the coast by subsea cables, what can
be done using alternate or direct current. A promising transmission configuration, but
not used commercially or experimentally, have the generating units connected in series
through the output terminals of their rectifiers. In this sense, it is possible to increase
the voltage without the need of an offshore substation, which probably reduce the costs
and increase the overall efficiency. In this work, the generating units are composed of a
wind turbine, a permanent magnet synchronous generator, a three-phase rectifier and a
dc solid state transformer, which has a full-bridge inverter, an air core transformer and
a diode rectifier. The transformer is essential to ensure galvanic insulation between the
generating unit components and the dc link. On the receiving end, a modular multilevel
converter is used as an inverter, which process all the energy supplied by the wind farm
and inject it into the mains. The first contribution of this work is the design of a dc
solid state transformer, with proper dimensions to the installation in a wind turbine,
using the FEMM software. Another contribution is a solution related to the modulation
strategy of the modular multilevel converter. It is used to mitigate problems related to
the unbalanced voltages on the positive and negative poles of the dc link, caused by the
ground position. Finally, it is investigated the operation of a system with two or more sets
of series connected units in parallel. In this configuration, there are overcurrent problems
in the sets and overvoltage in the generating units. In order to mitigate these problems, it
is proposed a control strategy based on the idea of virtual admittance. Simulations in the
PSCAD/EMTDC software are used to verify the operation of the series-connected wind
farm, as well as the proposed control strategies.
Description
Keywords
Conversão de energia eólica , Parques eólicos offshore conectados em série , Transmissão VSC-HVDC , Conversor multinível modular , Conversor NPC , Transformador de estado sólido CC , Wind energy conversion , Series-connected offshore wind farms , VSC-HVDC transmission , Modular multilevel converter , NPC converter , DC solid state transformer