Metodologias para representação do suporte de frequência por elos HVDC e avaliação de desempenho
Loading...
Date
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Universidade Federal de Juiz de Fora (UFJF)
DOI
Abstract
In its first part, this work presents an alternative way to evaluate convergence
problems using the principal component analysis (PCA) mathematical technique. This
methodology aims to identify failures in data entry or interactions between control devices
in the power flow. For comparison purposes, this technique is confronted with the modal
analysis by eigenvalues and eigenvectors. In the second part, a methodology is proposed
to include the participation of direct current links in the primary frequency control. The
different ways to vary the link power with frequency are discussed, with three models being
presented and integrated into the power flow: the conventional one, the Stab50 (used in
Itaipu) and an alternative model used to ensure voltage fluctuation suppression (VFS) on
adjacent AC buses. In this dissertation, the models and methodologies were developed in
MATLAB. The software Anatem, developed by CEPEL, was used to validate some results.
The results obtained through a case of the Brazilian South/Southeast system demonstrated
the ability of the ACP to identify conflicts in large systems. In addition, tests with a
3-area tutorial system showed the ability of the ACP to correctly identify mutual conflicts
between controls. In the case of frequency control, the results verified the accuracy of
the proposed models and pointed to the technique with SFT and variable frequency gain
as promising, since it was able to keep the voltage stable in the adjacent bars of the
link during the active power variation. Furthermore, this control model allowed precise
frequency support between power systems without the need for additional communication.
The results obtained through the test systems demonstrated ACP’s ability to
identify mutual conflicts between controls correctly. In the case of frequency control, the
results verified the accuracy of the proposed models and indicated the technique with VFS
as promising.
Description
Keywords
Citation
Endorsement
Review
Supplemented By
Referenced By
Creative Commons license
Except where otherwise noted, this item's license is described as Acesso Aberto