Estimação de estados em redes de distribuição de energia elétrica baseada em medições fasoriais
Loading...
Date
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Universidade Federal de Juiz de Fora
DOI
Abstract
This work presents a new approach to the State Estimation problem in Electrical Distribution
Networks using historical data loads and measurements obtained by Phasor Measurement
Units (PMUs). In this formulation voltage magnitudes and angles are chosen as state variables
and the problem is mathematically formulated as an optimization problem with equality and
inequality constraints. The objective function is formed by the quadratic sum of weighted
measurements residues, which are defined as the difference between the PMU measurements
and the calculated values. The equality constraints are defined as the zero injections of active
and reactive power at the no load buses. The inequality constraints are associated with active
and reactive powers of non-monitored buses, bounded by a given limit, superior or inferior in
relation to historical data loads (active and reactive powers).
Case studies are performed using a simple 10-bus test system, and the 33 and 84 buses IEEE
test systems. The data phasor measurements were obtained using a computer program that
calculates power flow. The state estimation results using the proposed methodology were
obtained through simulations in MATLAB environment and compared with the results of
power flow program for validation.
The use of synchronized phasor measurement at the beginning and at the end of the lateral
feeders of the distribution system associated with the use of inequality constraints for active
and reactive power for the non-monitored loads are the main contributions of this work.
Description
Citation
Endorsement
Review
Supplemented By
Referenced By
Rights and licensing
Acesso Aberto