Title: Estimação de estado harmônico para sistemas radiais de distribuição usando medição fasorial sincronizada
Author: Melo, Igor Delgado de
First Advisor: Pereira, José Luiz Rezende
Referee Member: Salgado, Roberto de Souza
Referee Member: Variz, Abílio Manuel
Referee Member: Duque, Carlos Augusto
Resumo: Este trabalho objetiva apresentar uma metodologia capaz de estimar os componentes harmônicos em sistemas de distribuição com topologia radial utilizando PMUs (Phasor Measurement Units). Os estados a serem estimados serão as correntes passantes em todas as linhas do sistema em coordenadas retangulares. Uma vez que essas correntes são obtidas, torna-se possível o cálculo de outras grandezas elétricas através das equações de fluxo de potência e leis de Kirchhoff. A metodologia considera poucas unidades de medição fasorial (as PMUs) instaladas efetuando a leitura dos sinais de tensões nodais e correntes nas linhas com distorção harmônica. A fim de restaurar a observabilidade do sistema por completo, são considerados dados históricos de demanda de potência ativa/reativa, os quais serão tratados como restrições de desigualdades excursionando entre um valor mínimo e máximo considerados em um problema de otimização não linear que visa diminuir a diferença entre os valores monitorados pelas PMUs e os calculados pela metodologia. As mencionadas restrições permitem ao estimador o acompanhamento das variações sofridas ao longo do tempo na curva de carga para a frequência fundamental e também para as demais frequências. A abordagem proposta neste trabalho considera a modelagem trifásica de equipamentos e linhas de distribuição, portanto, são modelados os efeitos de acoplamento mútuo entre fases e a operação não linear de equipamentos de eletrônica de potência tiristorizados. O método demonstra eficiência não apenas em estimar os componentes harmônicos de um certo espectro considerado no estudo, como também se mostra uma ferramenta prática de detecção e identificação de fontes harmônicas no sistema elétrico de potência, além de explicitar um exemplo prático do uso de PMUs no que tange ao monitoramento de redes de distribuição, carentes de acompanhamento em tempo real. A metodologia ainda se mostra capaz de ser aliada a grandes estudos contextualizados em qualidade de energia, uma vez que permite a estimação de índices de distorção harmônica.
Abstract: This work aims to present a methodology which is capable of estimating harmonic components for distribution systems with radial topology, using PMUs (Phasor Measurement Units). The estimated states will be all branch currents of the system expressed in rectangular coordinates. Once these currents are obtained, it is possible to calculate other electrical quantities using power flow equations and also Kirchhoff’s law. The methodology considers the installation of a few number of phasor measurement units which will measure voltage and branch currents signals distorted by harmonic sources. In order to make the whole system observable, historical data of active/reactive power demand will be treated as inequality constraints varying between minimum and maximum limits described in a non linear optimization problem, which aims to minimize the difference between the values monitored by PMUs and the ones calculated by the methodology. The already mentioned constraints allows the accompaniment of the variations occured in a typical load curve during a period of time for the fundamental frequency and also for their multiples, allowing the accompaniment of the harmonic load curve, normally unknown. The proposed approach considers a three-phase modelling of equipments and distribution lines, subject to their mutual coupling effects caused by mutual impedances between the lines. It will also be considered electronic-based devices using thyristors located along the distribution feeder, injecting harmonic currents in the system. The method demonstrates efficiency in estimating the harmonic states of the net and also in detecting and identifying harmonic sources in an eletric power system, besides showing a practical use of PMUs for the monitoring of distribution systems, lacking in information and real-time accompaniment. The method also enables the estimation of power quality indicators such as total harmonic distortion.
Keywords: Estimação de Estado Harmônico
Medição Fasorial Sincronizada
Qualidade de Energia
Harmônicos
Equipamentos FACTS
Sistemas de Distribuição
Smart Grids
Harmonic State Estimation
Phasor Measurement Units
Power Quality
Harmonics
FACTS devices
Distribution Systems
Smart Grids
CNPq: CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA
Language: por
Country: Brasil
Publisher: Universidade Federal de Juiz de Fora
Institution Initials: UFJF
Department: Faculdade de Engenharia
Program: Programa de Pós-graduação em Engenharia Elétrica
Access Type: Acesso Aberto
URI: https://repositorio.ufjf.br/jspui/handle/ufjf/234
Issue Date: 18-Sep-2015
Appears in Collections:Mestrado em Engenharia Elétrica (Dissertações)



Items in DSpace are protected by Creative Commons licenses, with all rights reserved, unless otherwise indicated.