Estimação de estados trifásica a quatro fios para sistemas de distribuição multiaterrados: uma abordagem considerando pseudomedidas associadas ao neutro
Loading...
Date
Journal Title
Journal ISSN
Volume Title
Publisher
Universidade Federal de Juiz de Fora (UFJF)
DOI
Abstract
Currently, there is an increasing need to monitor electrical quantities in distribution
networks. However, traditional state estimation techniques cannot be directly applied to
these networks due to intrinsic characteristics such as unbalanced loads, predominantly
radial topology, and a limited number of meters installed along medium voltage feeders.
In this complex scenario, in addition to real-time measurements, it is necessary to use
supplementary information to assist in estimating the operational state of the network.
Such information is referred to as pseudo-measurements and is traditionally associated with
active and reactive power values obtained through historical monthly energy consumption
data for each consumer.
Due to the scarcity of research considering three-phase four-wire state estimation
(SE) for distribution systems, this work presents a new approach to SE in multi-grounded
networks. In the proposed methodology, the state variable vector consists of branch
currents in rectangular coordinates, and measurements are obtained with the use of Phasor
Measurement Units (PMUs) installed along radial feeders. The three-phase four-wire
model is considered for network elements representing the neutral conductor and grounding
impedance.
An optimization problem is formulated to determine the operational state of
the system based on an objective function defined by the weighted least squares concept.
Pseudo-measurements related to loads are modeled by inequality constraints to compensate
for the lack of real-time measurements, assuming a scenario with a scarcity of phasor
meters that allow real-time monitoring.
To demonstrate the effectiveness of the proposed method, simulations are conducted
using the 21-bus Kersting test system and the modified 33-bus system, assuming different
meter placements, load scenarios, and grounding impedances. Analyses of the impact of
distributed generation on the 33-bus system are also included in the study. Additionally,
the impact of increased load on neutral voltage determination and phase imbalance will
be addressed to validate the effectiveness of the proposed method.
A significant contribution of this work is the addition of inequalities related to
the power dissipated in the neutral, aiding in the reduction of errors for all phases and
allowing for the estimation of neutral-to-earth voltage (NEV) and phase imbalance, with
reduced estimation errors.