Estimação da impedância de transferência baseada em ICA para redes com múltiplas fontes harmônicas
Loading...
Date
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Universidade Federal de Juiz de Fora (UFJF)
Abstract
Currently, the increasing use of nonlinear loads and power electronics-based equipment has significantly contributed to the rise of harmonic distortions in electrical signals.
This continuous growth in harmonic distortion levels in distribution electrical networks has
raised serious concerns for both utilities and system customers, as the presence of these
harmonic sources can compromise the efficiency of energy generation, transmission, and
utilization. Traditionally, the analysis of harmonic distortion contributions at a specific
point in the electrical system is conducted by considering only the contributions from the
load side and the main source side. However, for a more accurate and reliable evaluation,
it is essential to quantify the individual contributions of different harmonic sources. In
this context, this paper presents an innovative methodology to estimate harmonic transfer
impedances in power systems with multiple harmonic sources. The objective is to determine
the responsibility of each harmonic source for the total harmonic distortion at a specific
bus within the system, addressing a critical issue in the field of power quality. To achieve
this objective, it is necessary to estimate not only the individual harmonic sources but also
the transfer impedances between each source and the bus under analysis. Most methods to
solve this problem rely on proper network modeling or restrict harmonic source variations
to a single source at a time. The proposed methodology overcomes this limitation. For this
purpose, synchronized current and voltage phasors are measured at the bus under analysis.
After collecting the measurements, the Independent Component Analysis (ICA) method
is applied to estimate the Norton equivalent. The harmonic transfer impedance is then
determined using the information provided by ICA. To enhance the accuracy of harmonic
transfer impedance estimation, three procedures are employed to analyze the data of the
parameters provided by ICA over time, generating a well-conditioned system. Once the
harmonic transfer impedance is satisfactorily determined, the individual harmonic contributions, i.e., harmonic responsibilities, can be accurately estimated. The effectiveness and
performance of the method are demonstrated through computational simulations applied
to distribution and transmission systems. Furthermore, the methodology is validated using
real data collected from a Brazilian transmission system monitored by synchronized power
quality measurement units. The simulated results show that the Total Vector Error (TVE)
is less than 0.4%, and for the real data test, the TVE is less than 2%.
Description
Keywords
Qualidade de energia elétrica , Smart-grids , Estimação de impedância harmônica , Análise de componentes independentes , Responsabilidade harmônica , Transferência harmônica , Identificação de fontes , Electric power quality , Harmonic impedance estimation , Independent component analysis , Harmonic responsibility , Harmonic transfer
Citation
Collections
Endorsement
Review
Supplemented By
Referenced By
Creative Commons license
Except where otherwise noted, this item's license is described as Acesso Aberto