Previsão de carga elétrica em curto prazo utilizando combinação de estações meteorológicas
Loading...
Date
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Universidade Federal de Juiz de Fora (UFJF)
Abstract
Hourly-based load forecasts are necessary for the daily scheduling of the Electric
Power Supply Chain (EPSC), as for many players involved on the operation of energy
markets. Because of the impossibility of storing large volumes of electricity, it is desirable
for the supply to meet its demand on real time, which leads bad forecasts to unbalance the
whole system, causing from raises on the financial costs of the operations to equipment
failure.
Lately, many companies in the EPSC are updating their technologies in order
to become smart grids. With smart grid apparatuses, it is possible to use sensoring to
monitor the load in multiple points of the system, crossing many distinct geographical
areas. As the demanda of electrical energy is known to be weather-dependant, a new
challenge emerges: how to select and combine data from many available weather stations
in order to feed load forecasting models for a specific territory?
On this work, we use an heuristics to rank weather stations and introduce two new
methods for combining them, taking into account practical aspects such as geographical
factors.
For seven datasets, corresponding to load zones from the independente operator
system of the state of New York, USA, we test the proposed methods to compose the
inputs for neural networks. We also try a combination by the simple average, as it is
frequent on the literature. We carry on a sensitivity analysis for the networks injecting
noise to the exogenous data and compare the results to univariate time series benchmarks,
which depend only on the historical load.
We verify that, for most of the load zones for which the combination of two or
more weather stations is necessary in order to consider its weather characteristics, the two
introduced combination methods have the best median performance, and also appear to
be robust to noise in exogenous data. We also note that forecasting models may benefit
from taking into account practical order factors, such as geographical characteristics of
the load zone, in the forecasting models. Besides, results show that it is important to be
aware of the quality of secondary data, since from a certain noise level it may be of best
practice to work only with load data, for some of the experimented datasets.
Description
Citation
Collections
Endorsement
Review
Supplemented By
Referenced By
Creative Commons license
Except where otherwise noted, this item's license is described as Acesso Aberto