Proposta e implementação de uma Micro-PMU
Loading...
Date
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Universidade Federal de Juiz de Fora (UFJF)
DOI
Abstract
The present work proposes of a low cost Phasor Measurement Unity (PMU), for monitoring the power distribution system. The proposed meter can be connected at the low voltage level, making possible the monitoring of the distribution system and the transmission system. The algorithm used to compute the phasor estimation that composes the embedded software in the equipment uses the Savitzky-Golay filter to approximate the differentiation process, necessary in the frequency estimation of the fundamental component of the signal. The hardware of the equipment is composed by a microprocessor AMR TM4C1294NCPDT of Texas Instruments, a uBlox GPS NEO-6M module, a Wi-Fi ESP8266 module and an analog conditioning circuit. The synchronism of the measurements is guaranteed due to a pulse per second signal from the GPS module. For the transmission of the data generated by the PMU, the protocol suggested by the standard is used. The estimated parameters can be visualized in real time through the Synchrophasor Data Monitor Software. The results contemplate the tests required by the IEEE standard C37.118.1 and the analyses of the total vector error, frequency error and rate of change of frequency error. Finally, to attest the synchronism between different PMUs, a test in a Real Time Digital Simulator (RTDS) was made, where the 4 bus IEEE system was simulated. The difference of the angles estimated for different buses was computed and the obtained values were according to the expected.
Description
Keywords
PMU , Estimação fasorial , Sincrofasores , Savitzky-Golay , Savitzky-Golay , Processamento de sinais , GPS , OpenPDC , WAMS , IEEE C37 , 118 , Phasor estimation , Synchrophasor , Savitzky-Golay , Microprocessor , Signal processing , GPS , OpenPDC , WAMs , IEEE C37 , 118
Citation
Endorsement
Review
Supplemented By
Referenced By
Rights and licensing
Acesso Aberto